Actuators, Linear Actuators, Compact Actuators, Pneumatic Actuators, Actuators for Dampers, Rotary Actuators for Sluice Valves, Valves Actuators, Motorized Valves, Motorized Clamps Actuator On Butterfly Valve, Actuator On Globe Valve, Actuator With Integral Starter, Actuator With Spur Gear Box, Actuator With Worm Gear Box, Actuator On Sluice Valve, Flame Proof Actuator, Damper Actuator, QT Actuators ( Quarter Turn Actuators ), Electric Thrusters, Electronic Valve Positioners, Panel Mounted Electronic Positioner, Motorized Butterfly Valve, Motorized Sluice Valve, Fabricated Actuator Valve, Globe Valve, Dampers, Single Flap Butterfly Dampers, Multi Louvers Dampers, Spur Gear Box ( Multi Turn ) For Slice And Gate Valves, Spur Gear Box ( Quarter Turn ) For Butterfly, Ball & Plug Valves, Worm Gear Box
ELECTRONIC VALVE POSITIONERS PANEL MOUNTED
home products special applications about us sitemap infraqstructure contact us spcr

APPLICATION
TECHNICAL SPECIFICATIONS
PANEL MOUNTED ELECTRONIC POSITIONERS SERIES PP500 (Single Phase & Three Phase)
FRONT SIDE DETAILS : MODELS PP501/PP502/PP503 - SP/TP
REAR SIDE DETAILS & CONNECTION DIAGRAM

ELECTRONIC VALVE POSITIONERS PANEL MOUNTED
- SERIES PP500

Application:

Electronic Valve Positioner units are used for controlling the mechanical position of final control elements with respect to incoming commands received from the controllers such as PID/DCS/QCS etc. and also to give feed back signals.

The incoming control command in the form of 4-20mA/0-20mA or 0-10 V DC/ 0-5VDC is converted into 230 V AC 50 Hz or 110 V AC 50 Hz 1 Phase outputs by the positioner to run the actuator motor in forward & reverse directions. The positioner while generating the output signal also takes into account the present position of the final control element, dead band, feedback signal, time delay etc.

The Positioners are supplied in two different forms Field mounted and Panel mounted; for Single & Three phase requirements.

TOP

TECHNICAL SPECIFICATIONS

Power Supply :

230 V AC 50 Hz Standard ± 10%
110 V AC 50 Hz Optional

Control Signal (Input) & Retransmission Signal (Output)

4-20 mA DC Standard. 4 mA-Valve closed
20 mA-Valve opened.
0-20 mA DC
0-10 V DC
0-5 V DC
Optional.
NOTES:-
1) The Retransmission output signal is Self-powered with a load capacity of 500 W Maximum for current out put.
2) Use separate signal Isolator if Isolated output is required, Model SI 601 Opto-Galvanic Isolation between Input,     Output and Power supply.
    Rating : 2 KV.
3) It is possible to give Retransmission output signal in same or different form, than Input control signal.

TOP

PANEL MOUNTED ELECTRONIC POSITIONERS SERIES PP500
(Single Phase & Three Phase)

Feedback Signal :

MODEL Feed-back Signal from Actuator
PP 501 SP & TP 100-235 W ± 15 W - 3 Wire technique for automatic lead wire resistance compensation.-[100 W valve closed, 235 W - valve opened]
PP 502 SP & TP Inductive non contact type Potentiometer
LVDT / RVDT 0.5 to 4.5 V DC [ 0.5 V valve closed, 4.5 V valve opened]
PP 503 SP & TP 4-20 mA Two wire Transmitter ( Model PPT200 Located in the Actuator.) [ 4 mA-valve closed, 20 mA valve opened]

When the operational requirement is more precise & also the distance between the actuator & control system is more than 10 Meters , it is recommended to use Model PP 503 SP/TP instead of PP 501 SP/TP to avoid Electrical Noise Disturbances.

Position Indicator :-

To indicate Percentage opening of the final control element
Range - 0 - 100.0%
Indicator - 3 ½ Digit 12.7 mm height Red LED
Resolution - 0.1%
Accuracy - 0.2% ± 1 Digit. F.S.R.
Adjustment - Span / Zero adjustable in the range of 10% (Aprox.)

Control Features :-

  • Auto / Manual selection facility.
  • Open / Off / Close operating switch when selector switch is in Manual mode. A Potentiometer can be provided for Open / Close operation , as an option, instead of switch.
  • Time Delay (TD) adjustment in the range of 0.2 to 20 Second to adjust the time gap between command signal & it's acknowledgement , to avoid hunting. Clockwise rotation will increase the Time Delay.
  • Dead Band (DB) setting in the range of 1 to 10%. Clockwise rotation will increase the Dead Band.

Fault Indications :-

  • Fault LED ( I / P) : Fault LED Input glows when the control signal is absent or less than desired value e.g. 4 mA.
  • Fault LED ( F / B) : Fault LED Feedback glows when the feed back signal from the actuator is absent or incorrect.

Control / Calibration Adjustments :-

  • IND - Zero / Span adjustments for digital indicator , so to match percentage opening of the valve & other Parameters. Location on front side (Top)
  • Control - Zero / Span adjustment for control signal , so as to match them with mechanical position of the valve / feedback signal from the actuator. Location on front side . ( Bottom)
  • F.B. - Zero /Span adjustments for feedback signal , so as to match them with mechanical position of the valve / Control Signal from controller. Location on rear side ( Right Top)
  • R.X. - Zero / span adjustments for Retransmission output , so as to match them with other parameters. Location on rear side ( Left Bottom)

Other Details:-

Mounting Flush panel mounted with mounting clamps.
Size 96 X 96 X 125 mm , Cutout 92 X 92 mm
Protection Fuse for power supply : 100mA
Fuse for Relay Output : 1 Amp. (only for Single Phase Models )
Location : Rear Side.
Relay Rating 5 Amp at 230 V AC Resistive Load
Power consumption 5 V A Maximum
Operating Temperature 0 - 50°C
Relative Humidity 90% Rh Max. Non condensing
CMRR > 120db
NMRR > 80db
CMV 500 V AC/DC.
Weight 1 Kg (Approx.)
Recommended Calibration Check - 1 Year Normal
- 6 Months Critical Application.

TOP

FRONT SIDE DETAILS : MODELS PP501/PP502/PP503 - SP/TP

    FRONT SIDE DETAILS
  1. Zero / Span adjustments for Digital Indicator.
  2. Digital Indicator to show % opening.
  3. Two position switch for selection of Auto / Manual mode.
  4. Three Position switch to Open / Off / Close the actuator.
  5. LED indication to show Open / Close Command going to the actuator.
  6. Fault LED glows when Input signal is absent or below 4mA.
  7. Fault LED glows when Feed back signal is absent, or incorrect.
  8. Zero / Span Adjustments to match control signal with Actuator Travel / Feed back.
  9. Time Delay adjustment Pot 0.2 to 20Sec.
    (clockwise rotation will increase the time delay.)
  10. Dead Band adjustment Pot 1 to 10%
    (clockwise rotation will increase the Dead band )